Fire & Smoke Damper Testing Requirements

The NFPA 80 / 105 damper schedule — the operational test one year after installation, then every 4 years (6 in hospitals) — and the annual access-panel check your staff can do.

  1. 1Address
  2. 2Facility
  3. 3Systems
  4. 4Details
  5. 5Dates
  6. 6Review
Facility address

Printed on every output — the calendar header and log sheets. You can skip it and add it later.

Free · No signup. Your dates and facility details stay on your device — every calculation happens on your device.

NFPA 80 / NFPA 105 schedule

Every requirement carries its code section and the edition it was verified against. ★ = qualified in-house under the national code, but licensing commonly required locally — confirm with your AHJ.

Fire and smoke damper testing comes from NFPA 80 and NFPA 105 — consensus standards, not law. They bind your building only where your state, AHJ, accreditor or insurer has adopted them, at the edition adopted, and only where a duct penetrates a rated assembly. Hospitals certified by CMS are surveyed against the 2012 Life Safety Code, which references earlier editions of NFPA 80 and NFPA 105 than the 2022 edition cited below; confirm with your surveyor or AHJ which edition and which interval applies to you, and whether a waiver declaration is expected at your entrance conference. The 6-year hospital cycle is a conditional allowance, not an automatic one. Neither standard fixes how long you keep the record — your state, accreditor or insurer sets that, which is why the table says so rather than printing a number. Testing is by a qualified person; whether that means a licensed contractor is a local licensing question, and the damper’s listing and the manufacturer’s instructions govern how it is tested.

TaskFrequencyWho may performCode (edition)Record
Fire, smoke and combination damper operational test — one year after installation, then every 4 yearsEvery 4 yearsIn-house (qualified)NFPA 80 §19.4 / NFPA 105 (2022)Damper log with location, ID, pass/fail and corrective action.
Fire, smoke and combination damper operational test — one year after installation, then every 6 years (hospitals)Every 6 yearsIn-house (qualified)NFPA 80 §19.4 / NFPA 105 (hospital 6-year interval) (2022)Written report listing every damper by location with pass/fail
Damper access panels unobstructed; no visible damage or blocked linkageAnnualIn-house (basic)NFPA 80 §19.4 (access) (2022)Rounds log.

Record it: Log the annual access-panel check · The other NFPA 80 assembly: fire doors · File the damper contractor’s certificate

Other schedules: NFPA 101 / NFPA 105 · NFPA 25 (water supply) · NFPA 25 · NFPA 72 · NFPA 96

National consensus-standard baseline with the edition noted per item. Your state, fire marshal, or accrediting body may require more frequent service or licensed personnel where a qualified person is shown. General information, not legal or engineering advice — confirm with your AHJ.

Questions people ask

How often does NFPA 80 / NFPA 105 require inspection?
NFPA 80 / NFPA 105 sets a schedule from every 4 years, every 6 years, annual intervals. The full task-by-task table with code sections and who may perform each task is shown above, and the calendar builder dates it from your real last-completed dates.
Which of these tasks can be done in-house?
Tasks marked Tier 1 or Tier 2 can be performed by trained facility staff with documentation under the national code. Tier 3 tasks require a certified or licensed professional. Starred tasks are qualified in-house under the national code but licensing is commonly required locally — confirm with your AHJ.