Emergency & Exit Lighting Testing (NFPA 101)

The NFPA 101 emergency and exit lighting schedule — the monthly 30-second test and annual 90-minute discharge, both in-house-eligible.

  1. 1Address
  2. 2Facility
  3. 3Systems
  4. 4Details
  5. 5Dates
  6. 6Review
Facility address

Printed on every output — the calendar header and log sheets. You can skip it and add it later.

Free · No signup. Everything is computed on your device — nothing is uploaded.

NFPA 101 schedule

Every requirement carries its code section and the edition it was verified against. ★ = qualified in-house under the national code, but licensing commonly required locally — confirm with your AHJ.

TaskFrequencyWho may performCode (edition)Record
Emergency lighting — 30-second functional testMonthlyIn-house (basic)NFPA 101 §7.9.3 (monthly 30-sec) (2021)Log
Exit sign illumination checkMonthlyIn-house (basic)NFPA 101 §7.10 (2021)Log
90-minute full battery discharge testAnnualIn-house (qualified)NFPA 101 §7.9.3 (annual 90-min) (2021)Test record

Other schedules: NFPA 25 · NFPA 72 · NFPA 96 · NFPA 110 · NFPA 80

National consensus-standard baseline with the edition noted per item. Your state, fire marshal, or accrediting body may require more frequent service or licensed personnel where a qualified person is shown. General information, not legal or engineering advice — confirm with your AHJ.