Emergency & Exit Lighting Testing (NFPA 101)
The NFPA 101 emergency and exit lighting schedule — the monthly 30-second test and annual 90-minute discharge, both in-house-eligible.
- 1Address
- 2Facility
- 3Systems
- 4Details
- 5Dates
- 6Review
Free · No signup. Everything is computed on your device — nothing is uploaded.
NFPA 101 schedule
Every requirement carries its code section and the edition it was verified against. ★ = qualified in-house under the national code, but licensing commonly required locally — confirm with your AHJ.
| Task | Frequency | Who may perform | Code (edition) | Record |
|---|---|---|---|---|
| Emergency lighting — 30-second functional test | Monthly | In-house (basic) | NFPA 101 §7.9.3 (monthly 30-sec) (2021) | Log |
| Exit sign illumination check | Monthly | In-house (basic) | NFPA 101 §7.10 (2021) | Log |
| 90-minute full battery discharge test | Annual | In-house (qualified) | NFPA 101 §7.9.3 (annual 90-min) (2021) | Test record |
Other schedules: NFPA 25 · NFPA 72 · NFPA 96 · NFPA 110 · NFPA 80
National consensus-standard baseline with the edition noted per item. Your state, fire marshal, or accrediting body may require more frequent service or licensed personnel where a qualified person is shown. General information, not legal or engineering advice — confirm with your AHJ.