Rhode Island survey readiness

What Rhode Island Department of Health can ask you for, each line cited — and the ones you can't yet produce.

The building

Rhode Island requirements loaded — the rules below are Rhode Island’s own.

0 of 29 ready.

29 of the outstanding items are the ones a survey opens with.

Rhode IslandAssisted Living Residence

What Rhode Island Department of Health can ask for, each cited. Checked July 2026.

Goes in the planIs the section written, and does it say what the rule requires?

A Rhode Island assisted living license application must contain affirmative evidence of the ability to comply with the regulations and with federal, state and local laws on fire safety and other health and safety requirements. Fire safety is proved at application, not merely inspected later.

216-RICR-40-10-2 · Rhode Island Department of Health

Produce this →

Must be filed or approvedWas it sent — and where approval is required, was it approved?

A Rhode Island assisted living license application must contain affirmative evidence of the ability to comply with the regulations and with federal, state and local laws on fire safety and other health and safety requirements. Fire safety is proved at application, not merely inspected later.

216-RICR-40-10-2 · Rhode Island Department of Health

Produce this →

Must be done, on a scheduleWhen did it last happen, and was that inside the interval?

Drills at the required frequency: Simulated drills testing the EFFECTIVENESS of the emergency preparedness plan at least semi-annually, with written reports and an evaluation of every drill kept by the residence.

216-RICR-40-10-2 (Licensing Assisted Living Residences); administrator certification at 216-RICR-40-05-18 · Rhode Island Department of Health

Produce this →

Records to retainHow far back can you produce the records?

Drills at the required frequency: Simulated drills testing the EFFECTIVENESS of the emergency preparedness plan at least semi-annually, with written reports and an evaluation of every drill kept by the residence.

216-RICR-40-10-2 (Licensing Assisted Living Residences); administrator certification at 216-RICR-40-05-18 · Rhode Island Department of Health

Produce this →

Life-safety systems

The code-based tests a life-safety survey opens with. These are the starred ones — the full schedule is the compliance calendar.

Test record

NFPA 72 Table 14.4.3.2 (supervisory device testing) (2022) · national · keep: Minimum 5 years

Produce this →

Certificate + inspection report

NFPA 72 §14.4 (annual ITM) (2022) · national · keep: Minimum 5 years

Produce this →

Test record

NFPA 25 §5.3.3 / §13.7 (2023) · national · keep: Life of system

Produce this →

Static + residual pressures; compare to prior; >10% drop investigated

NFPA 25 §5.3.3 (main drain quarterly where sole supply passes through backflow preventer or PRV) (2023) · national · keep: Life of system

Produce this →

Pressures vs prior year

NFPA 25 §13.2.5 (2023) · national · keep: Life of system

Produce this →

Written record for AHJ

NFPA 80 §5.2.1 (annual, 13 criteria) (2022) · national · keep: 3 years

Produce this →

Report

NFPA 110 §8.3.1 (2022) · national · keep: Per authority

Produce this →

Damper log with location, ID, pass/fail and corrective action.

NFPA 80 §19.4 / NFPA 105 Ch. 6 (2022) · national · keep: Until the next test, minimum 3 years

Produce this →

Written report listing every damper by location with pass/fail

NFPA 80 §19.4 / NFPA 105 Ch. 6 (hospital 6-year interval) (2022) · national · keep: Until the next test, minimum 3 years

Produce this →

Monthly firefighter service log.

ASME A17.1 §8.6.11.1 (2019) · state-governed · keep: Minimum 3 years

Produce this →

Trip test report with trip time and water delivery time.

NFPA 25 §13.4.4.2.2 (3-year full trip) (2020) · national · keep: Minimum 3 years

Produce this →

Tank inspection report.

NFPA 25 §9.2.6 (interior inspection) (2020) · national · keep: Until the next interior inspection

Produce this →

Smoke control test report with fan and damper positions.

NFPA 92 §8.4.2 (dedicated: semiannual) (2021) · national · keep: Minimum 3 years

Produce this →

Signed drill sheet: date, time, shift, participants, evacuation time.

NFPA 101 §19.7.1 / CMS LSC (2012) · national · keep: Survey cycle

Produce this →

Signed drill sheet.

NFPA 101 §19.7.1 / CMS LSC (2012) · national · keep: Survey cycle

Produce this →

Signed drill sheet.

NFPA 101 §19.7.1 / CMS LSC (2012) · national · keep: Survey cycle

Produce this →

After-action report and improvement plan.

42 CFR §483.73(d)(2) (—) · national · keep: Minimum 3 years

Produce this →

Signed HVA.

42 CFR §483.73(a)(1) (—) · national · keep: Minimum 3 years

Produce this →

Dated plan revision.

42 CFR §483.73(a) (—) · national · keep: Minimum 3 years

Produce this →

Dated plan revision and team roster.

ASHRAE 188 / CMS QSO-17-30 (2018) · national · keep: Survey cycle

Produce this →

Readings against control limits.

ASHRAE 188 §7 (2018) · national · keep: Survey cycle

Produce this →

Receptacle test record by room.

NFPA 99 §6.3.3.2 (12-month interval applies to receptacles not listed hospital grade) (2021) · national · keep: Minimum 3 years

Produce this →

Rounds log.

NFPA 101 §19.3.6 (2012) · national · keep: Survey cycle

Produce this →

Barrier log with locations.

NFPA 101 §19.3.7 (2012) · national · keep: Survey cycle

Produce this →

Photo of posting with date.

29 CFR §1904.32(b)(6) (—) · national · keep: 5 years

Produce this →

Temperature log by unit.

FDA Food Code §3-501.16 (cold holding, as adopted by your state) (2022) · state-governed · keep: Minimum 1 year

Produce this →

Inspection report and corrective-action record.

Local AHJ (—) · local · keep: Minimum 3 years

Produce this →

What Rhode Island requires

Assisted Living ResidenceAssisted living / residential care
  • Your fire and evacuation drill records for the period. Drills at the required frequency: Simulated drills testing the EFFECTIVENESS of the emergency preparedness plan at least semi-annually, with written reports and an evaluation of every drill kept by the residence. 216-RICR-40-10-2 (Licensing Assisted Living Residences); administrator certification at 216-RICR-40-05-18
  • Fire safety compliance is a licensing precondition. A Rhode Island assisted living license application must contain affirmative evidence of the ability to comply with the regulations and with federal, state and local laws on fire safety and other health and safety requirements. Fire safety is proved at application, not merely inspected later. 216-RICR-40-10-2
Rhode Island Department of Health · checked July 2026

The evidence, and where it comes from

Every item above needs something you can hand over. The Rhode Island fire drill log produces the drill record at the frequency this state sets, the emergency plan builder writes the plan itself from the same research, and the compliance calendar puts the life-safety tests on dates. Anything you record against the building shows up on the checklist already ticked.

A self-assessment against published rules, not a compliance determination. CompliMaint issues nothing — Rhode Island Department of Health and your authority having jurisdiction do. Requirements we could not verify are absent rather than guessed at.