Michigan survey readiness

What Michigan Dept. of Licensing and Regulatory Affairs (LARA) — Bureau of Community and Health Systems can ask you for, each line cited — and the ones you can't yet produce.

The building

Michigan requirements loaded — the rules below are Michigan’s own.

0 of 29 ready.

28 of the outstanding items are the ones a survey opens with.

MichiganAdult Foster Care Facility

What Michigan Dept. of Licensing and Regulatory Affairs (LARA) — Bureau of Community and Health Systems can ask for, each cited. Checked July 2026.

Must be done, on a scheduleWhen did it last happen, and was that inside the interval?

Drills at the required frequency: Four fire drills a year, two of them during sleeping hours. Separately the licensee must practice the emergency preparedness plan — including the fire safety plan — at least once a quarter on EACH shift, counted against Michigan's named shifts of 7am–3pm, 3pm–11pm and 11pm–7am.

Mich. Admin. Code R 400.601 et seq. (adult foster care) · Michigan Dept. of Licensing and Regulatory Affairs (LARA) — Bureau of Community and Health Systems · keep: Records of emergency preparedness plan practices maintained for 2 years.

Produce this →

Records to retainHow far back can you produce the records?

Drills at the required frequency: Four fire drills a year, two of them during sleeping hours. Separately the licensee must practice the emergency preparedness plan — including the fire safety plan — at least once a quarter on EACH shift, counted against Michigan's named shifts of 7am–3pm, 3pm–11pm and 11pm–7am.

Mich. Admin. Code R 400.601 et seq. (adult foster care) · Michigan Dept. of Licensing and Regulatory Affairs (LARA) — Bureau of Community and Health Systems · keep: Records of emergency preparedness plan practices maintained for 2 years.

Produce this →

Records of emergency preparedness plan practices maintained for 2 years.

Mich. Admin. Code R 400.601 et seq. (adult foster care) · Michigan Dept. of Licensing and Regulatory Affairs (LARA) — Bureau of Community and Health Systems · keep: Records of emergency preparedness plan practices maintained for 2 years.

Produce this →

Life-safety systems

The code-based tests a life-safety survey opens with. These are the starred ones — the full schedule is the compliance calendar.

Test record

NFPA 72 Table 14.4.3.2 (supervisory device testing) (2022) · national · keep: Minimum 5 years

Produce this →

Certificate + inspection report

NFPA 72 §14.4 (annual ITM) (2022) · national · keep: Minimum 5 years

Produce this →

Test record

NFPA 25 §5.3.3 / §13.7 (2023) · national · keep: Life of system

Produce this →

Static + residual pressures; compare to prior; >10% drop investigated

NFPA 25 §5.3.3 (main drain quarterly where sole supply passes through backflow preventer or PRV) (2023) · national · keep: Life of system

Produce this →

Pressures vs prior year

NFPA 25 §13.2.5 (2023) · national · keep: Life of system

Produce this →

Written record for AHJ

NFPA 80 §5.2.1 (annual, 13 criteria) (2022) · national · keep: 3 years

Produce this →

Report

NFPA 110 §8.3.1 (2022) · national · keep: Per authority

Produce this →

Damper log with location, ID, pass/fail and corrective action.

NFPA 80 §19.4 / NFPA 105 Ch. 6 (2022) · national · keep: Until the next test, minimum 3 years

Produce this →

Written report listing every damper by location with pass/fail

NFPA 80 §19.4 / NFPA 105 Ch. 6 (hospital 6-year interval) (2022) · national · keep: Until the next test, minimum 3 years

Produce this →

Monthly firefighter service log.

ASME A17.1 §8.6.11.1 (2019) · state-governed · keep: Minimum 3 years

Produce this →

Trip test report with trip time and water delivery time.

NFPA 25 §13.4.4.2.2 (3-year full trip) (2020) · national · keep: Minimum 3 years

Produce this →

Tank inspection report.

NFPA 25 §9.2.6 (interior inspection) (2020) · national · keep: Until the next interior inspection

Produce this →

Smoke control test report with fan and damper positions.

NFPA 92 §8.4.2 (dedicated: semiannual) (2021) · national · keep: Minimum 3 years

Produce this →

Signed drill sheet: date, time, shift, participants, evacuation time.

NFPA 101 §19.7.1 / CMS LSC (2012) · national · keep: Survey cycle

Produce this →

Signed drill sheet.

NFPA 101 §19.7.1 / CMS LSC (2012) · national · keep: Survey cycle

Produce this →

Signed drill sheet.

NFPA 101 §19.7.1 / CMS LSC (2012) · national · keep: Survey cycle

Produce this →

After-action report and improvement plan.

42 CFR §483.73(d)(2) (—) · national · keep: Minimum 3 years

Produce this →

Signed HVA.

42 CFR §483.73(a)(1) (—) · national · keep: Minimum 3 years

Produce this →

Dated plan revision.

42 CFR §483.73(a) (—) · national · keep: Minimum 3 years

Produce this →

Dated plan revision and team roster.

ASHRAE 188 / CMS QSO-17-30 (2018) · national · keep: Survey cycle

Produce this →

Readings against control limits.

ASHRAE 188 §7 (2018) · national · keep: Survey cycle

Produce this →

Receptacle test record by room.

NFPA 99 §6.3.3.2 (12-month interval applies to receptacles not listed hospital grade) (2021) · national · keep: Minimum 3 years

Produce this →

Rounds log.

NFPA 101 §19.3.6 (2012) · national · keep: Survey cycle

Produce this →

Barrier log with locations.

NFPA 101 §19.3.7 (2012) · national · keep: Survey cycle

Produce this →

Photo of posting with date.

29 CFR §1904.32(b)(6) (—) · national · keep: 5 years

Produce this →

Temperature log by unit.

FDA Food Code §3-501.16 (cold holding, as adopted by your state) (2022) · state-governed · keep: Minimum 1 year

Produce this →

Inspection report and corrective-action record.

Local AHJ (—) · local · keep: Minimum 3 years

Produce this →

What Michigan requires

Adult Foster Care FacilityGroup home / residential care home
  • Your fire and evacuation drill records for the period. Drills at the required frequency: Four fire drills a year, two of them during sleeping hours. Separately the licensee must practice the emergency preparedness plan — including the fire safety plan — at least once a quarter on EACH shift, counted against Michigan's named shifts of 7am–3pm, 3pm–11pm and 11pm–7am. Mich. Admin. Code R 400.601 et seq. (adult foster care)
  • Records going back as far as the rule requires. Records of emergency preparedness plan practices maintained for 2 years. Mich. Admin. Code R 400.601 et seq. (adult foster care)
Michigan Dept. of Licensing and Regulatory Affairs (LARA) — Bureau of Community and Health Systems · checked July 2026
Home for the Aged (HFA)Assisted living / residential care
  • Named failure modes, not just 'emergency'. Michigan requires a written plan and procedure for fire, explosion, LOSS OF HEAT, loss of power, loss of water, or other emergency. Loss of heat is named separately — a Michigan winter outage is its own scenario, not a footnote to power failure. Mich. Admin. Code R 325.1976
Michigan Dept. of Licensing and Regulatory Affairs (LARA) — Bureau of Community and Health Systems · checked July 2026

The evidence, and where it comes from

Every item above needs something you can hand over. The Michigan fire drill log produces the drill record at the frequency this state sets, the emergency plan builder writes the plan itself from the same research, and the compliance calendar puts the life-safety tests on dates. Anything you record against the building shows up on the checklist already ticked.

Everything else we’ve researched about Michigan

Same state, the problems either side of this one. Each carries its own statute and the date we last checked it.

A self-assessment against published rules, not a compliance determination. CompliMaint issues nothing — Michigan Dept. of Licensing and Regulatory Affairs (LARA) — Bureau of Community and Health Systems and your authority having jurisdiction do. Requirements we could not verify are absent rather than guessed at.