Alaska survey readiness

What Alaska Department of Health — Division of Health Care Services, Residential Licensing can ask you for, each line cited — and the ones you can't yet produce.

The building

Alaska requirements loaded — the rules below are Alaska’s own.

0 of 30 ready.

30 of the outstanding items are the ones a survey opens with.

AlaskaAssisted Living Home

What Alaska Department of Health — Division of Health Care Services, Residential Licensing can ask for, each cited. Checked July 2026.

Goes in the planIs the section written, and does it say what the rule requires?

The emergency preparedness plan must include procedures for other emergency situations or natural disasters that may affect the home, including — as appropriate — tsunami, flooding and earthquake emergencies. Alaska names all three because all three are live: the 2018 Anchorage earthquake and the Pacific tsunami risk on the southern coast are both ordinary planning assumptions here.

7 AAC 75.290 / 7 AAC 10.1010 · Alaska Department of Health — Division of Health Care Services, Residential Licensing

Produce this →

Alaska allows the department to grant a general variance where an alternative means acceptable to the department satisfies the purpose of the requirement and still protects the health, safety and welfare of the people served. This matters more in Alaska than anywhere else: a home in a community with no road access cannot evacuate to a named receiving facility the way the rule contemplates, and the variance is the lawful path rather than quiet non-compliance.

7 AAC 75 (general variance) · Alaska Department of Health — Division of Health Care Services, Residential Licensing

Produce this →

Must be done, on a scheduleWhen did it last happen, and was that inside the interval?

Drills at the required frequency: Complete evacuation of the home at least once each year for each shift. The alternative is available only if the home conducts evacuations under the alternative provisions AND holds an emergency evacuation plan approved by the STATE FIRE MARSHAL — or by a municipality to which the fire marshal has deferred building fire safety inspection and enforcement.

7 AAC 75.270 (life and fire safety); 7 AAC 75.290 (emergency situations); life and fire safety standard at 7 AAC 10.1010 · Alaska Department of Health — Division of Health Care Services, Residential Licensing

Produce this →

Records to retainHow far back can you produce the records?

Drills at the required frequency: Complete evacuation of the home at least once each year for each shift. The alternative is available only if the home conducts evacuations under the alternative provisions AND holds an emergency evacuation plan approved by the STATE FIRE MARSHAL — or by a municipality to which the fire marshal has deferred building fire safety inspection and enforcement.

7 AAC 75.270 (life and fire safety); 7 AAC 75.290 (emergency situations); life and fire safety standard at 7 AAC 10.1010 · Alaska Department of Health — Division of Health Care Services, Residential Licensing

Produce this →

Life-safety systems

The code-based tests a life-safety survey opens with. These are the starred ones — the full schedule is the compliance calendar.

Test record

NFPA 72 Table 14.4.3.2 (supervisory device testing) (2022) · national · keep: Minimum 5 years

Produce this →

Certificate + inspection report

NFPA 72 §14.4 (annual ITM) (2022) · national · keep: Minimum 5 years

Produce this →

Test record

NFPA 25 §5.3.3 / §13.7 (2023) · national · keep: Life of system

Produce this →

Static + residual pressures; compare to prior; >10% drop investigated

NFPA 25 §5.3.3 (main drain quarterly where sole supply passes through backflow preventer or PRV) (2023) · national · keep: Life of system

Produce this →

Pressures vs prior year

NFPA 25 §13.2.5 (2023) · national · keep: Life of system

Produce this →

Written record for AHJ

NFPA 80 §5.2.1 (annual, 13 criteria) (2022) · national · keep: 3 years

Produce this →

Report

NFPA 110 §8.3.1 (2022) · national · keep: Per authority

Produce this →

Damper log with location, ID, pass/fail and corrective action.

NFPA 80 §19.4 / NFPA 105 Ch. 6 (2022) · national · keep: Until the next test, minimum 3 years

Produce this →

Written report listing every damper by location with pass/fail

NFPA 80 §19.4 / NFPA 105 Ch. 6 (hospital 6-year interval) (2022) · national · keep: Until the next test, minimum 3 years

Produce this →

Monthly firefighter service log.

ASME A17.1 §8.6.11.1 (2019) · state-governed · keep: Minimum 3 years

Produce this →

Trip test report with trip time and water delivery time.

NFPA 25 §13.4.4.2.2 (3-year full trip) (2020) · national · keep: Minimum 3 years

Produce this →

Tank inspection report.

NFPA 25 §9.2.6 (interior inspection) (2020) · national · keep: Until the next interior inspection

Produce this →

Smoke control test report with fan and damper positions.

NFPA 92 §8.4.2 (dedicated: semiannual) (2021) · national · keep: Minimum 3 years

Produce this →

Signed drill sheet: date, time, shift, participants, evacuation time.

NFPA 101 §19.7.1 / CMS LSC (2012) · national · keep: Survey cycle

Produce this →

Signed drill sheet.

NFPA 101 §19.7.1 / CMS LSC (2012) · national · keep: Survey cycle

Produce this →

Signed drill sheet.

NFPA 101 §19.7.1 / CMS LSC (2012) · national · keep: Survey cycle

Produce this →

After-action report and improvement plan.

42 CFR §483.73(d)(2) (—) · national · keep: Minimum 3 years

Produce this →

Signed HVA.

42 CFR §483.73(a)(1) (—) · national · keep: Minimum 3 years

Produce this →

Dated plan revision.

42 CFR §483.73(a) (—) · national · keep: Minimum 3 years

Produce this →

Dated plan revision and team roster.

ASHRAE 188 / CMS QSO-17-30 (2018) · national · keep: Survey cycle

Produce this →

Readings against control limits.

ASHRAE 188 §7 (2018) · national · keep: Survey cycle

Produce this →

Receptacle test record by room.

NFPA 99 §6.3.3.2 (12-month interval applies to receptacles not listed hospital grade) (2021) · national · keep: Minimum 3 years

Produce this →

Rounds log.

NFPA 101 §19.3.6 (2012) · national · keep: Survey cycle

Produce this →

Barrier log with locations.

NFPA 101 §19.3.7 (2012) · national · keep: Survey cycle

Produce this →

Photo of posting with date.

29 CFR §1904.32(b)(6) (—) · national · keep: 5 years

Produce this →

Temperature log by unit.

FDA Food Code §3-501.16 (cold holding, as adopted by your state) (2022) · state-governed · keep: Minimum 1 year

Produce this →

Inspection report and corrective-action record.

Local AHJ (—) · local · keep: Minimum 3 years

Produce this →

What Alaska requires

Assisted Living HomeAssisted living / residential care
  • Your fire and evacuation drill records for the period. Drills at the required frequency: Complete evacuation of the home at least once each year for each shift. The alternative is available only if the home conducts evacuations under the alternative provisions AND holds an emergency evacuation plan approved by the STATE FIRE MARSHAL — or by a municipality to which the fire marshal has deferred building fire safety inspection and enforcement. 7 AAC 75.270 (life and fire safety); 7 AAC 75.290 (emergency situations); life and fire safety standard at 7 AAC 10.1010
  • Tsunami, flooding and earthquake named in the rule. The emergency preparedness plan must include procedures for other emergency situations or natural disasters that may affect the home, including — as appropriate — tsunami, flooding and earthquake emergencies. Alaska names all three because all three are live: the 2018 Anchorage earthquake and the Pacific tsunami risk on the southern coast are both ordinary planning assumptions here. 7 AAC 75.290 / 7 AAC 10.1010
  • A general variance, for when the standard method cannot work. Alaska allows the department to grant a general variance where an alternative means acceptable to the department satisfies the purpose of the requirement and still protects the health, safety and welfare of the people served. This matters more in Alaska than anywhere else: a home in a community with no road access cannot evacuate to a named receiving facility the way the rule contemplates, and the variance is the lawful path rather than quiet non-compliance. 7 AAC 75 (general variance)
Alaska Department of Health — Division of Health Care Services, Residential Licensing · checked July 2026

The evidence, and where it comes from

Every item above needs something you can hand over. The Alaska fire drill log produces the drill record at the frequency this state sets, the emergency plan builder writes the plan itself from the same research, and the compliance calendar puts the life-safety tests on dates. Anything you record against the building shows up on the checklist already ticked.

A self-assessment against published rules, not a compliance determination. CompliMaint issues nothing — Alaska Department of Health — Division of Health Care Services, Residential Licensing and your authority having jurisdiction do. Requirements we could not verify are absent rather than guessed at.