Smoke detector & fire alarm test log

Equipment record

Every device, where it is, and what happened when you tested it — the record an owner or operator keeps.

The building

An owner/operator record of devices you tested. It is NOT the annual system inspection and test, the semi-annual component inspection, or detector sensitivity testing — those are separate exercises, commonly by a qualified or licensed technician, and they produce a certificate and an inspection report rather than a log. Nothing here performs or certifies any of them. How often YOUR devices must be tested, and by whom, depends on the code your jurisdiction adopted, your occupancy, the manufacturer's instructions and your AHJ — and, for carbon monoxide devices in particular, on state law this tool does not cover.

Where the reference figures come from

Panel visual — trouble/supervisory indicators, power, ground faults. Walk to the fire alarm panel and read it. The screen should say normal — no trouble, supervisory or alarm lights, and no ground-fault warning. If something is lit, write down the exact message before anyone clears it. NFPA 72 §14.3 (visual inspection), 2022 edition · record: log entry · retention: minimum 5 years · checked July 2026

Pull stations & notification appliances unobstructed, undamaged, in place. Walk the building and look at every pull station, horn and strobe. Nothing parked in front of them, nothing painted over, nothing missing or hanging off the wall. NFPA 72 §14.3, 2022 edition · record: log entry · retention: minimum 5 years · checked July 2026

This log is not: Full system test — control equipment, initiating devices, notification, HVAC shutdown (NFPA 72 §14.4 (annual ITM)); Smoke detector sensitivity test (calibrated equipment) (NFPA 72 §14.4.5 (sensitivity)); Component visual inspections per Table 14.3.1 (NFPA 72 Table 14.3.1).

This is the national consensus baseline, with the edition each figure was checked against. Whether it applies to your building — and at what frequency — depends on the code edition your jurisdiction has adopted, your occupancy, your equipment's listing, the manufacturer's instructions and your authority having jurisdiction. Confirm it with them. This tool records what you did; it makes no determination that any facility is compliant.

The devices

One card per device. Your list is kept for this building, so next time you open the tool and start checking rather than typing.

Visual check
Sounds when testedThe test button, or the method the manufacturer specifies.
Power / status indicator normal
In place, mounted correctly, undamaged
Unobstructed — nothing painted over, covered or stored against it
Within the manufacturer's replacement ageN/A where the device carries no date you can read.

What this is, and what it is not

This is an owner or operator record: the devices you have, where they are, and what happened when you tested them. It is deliberately not a fire-alarm inspection certificate, and it does not pretend to be one.

Separate exercises, not this log: Full system test — control equipment, initiating devices, notification, HVAC shutdown (NFPA 72 §14.4 (annual ITM)); Smoke detector sensitivity test (calibrated equipment) (NFPA 72 §14.4.5 (sensitivity)); Component visual inspections per Table 14.3.1 (NFPA 72 Table 14.3.1). Those produce a certificate and an inspection report, and where your jurisdiction requires a qualified or licensed person to carry them out, this log does not change that.

No frequency is asserted

How often your devices must be tested, and by whom, depends on the code your jurisdiction adopted, your occupancy, the manufacturer’s instructions and your AHJ — and for carbon monoxide devices, frequently on state law, which this tool does not cover. The reference rows below say what the national standard describes for the routine visual checks; they are shown with their edition and the date they were last checked, and they are not a statement about your building.

Panel visual — trouble/supervisory indicators, power, ground faults. Walk to the fire alarm panel and read it. The screen should say normal — no trouble, supervisory or alarm lights, and no ground-fault warning. If something is lit, write down the exact message before anyone clears it. NFPA 72 §14.3 (visual inspection), 2022 edition. Record: log entry. Retention: minimum 5 years.

Pull stations & notification appliances unobstructed, undamaged, in place. Walk the building and look at every pull station, horn and strobe. Nothing parked in front of them, nothing painted over, nothing missing or hanging off the wall. NFPA 72 §14.3, 2022 edition. Record: log entry. Retention: minimum 5 years.

This is the national consensus baseline, with the edition each figure was checked against. Whether it applies to your building — and at what frequency — depends on the code edition your jurisdiction has adopted, your occupancy, your equipment's listing, the manufacturer's instructions and your authority having jurisdiction. Confirm it with them. This tool records what you did; it makes no determination that any facility is compliant.

Why an inventory rather than a single sheet

A device that fails is a device you have to find again. Listing them by ID and location once — the list stays with the building — means the record names the unit in room 214 rather than saying “one detector failed”, and next month you start testing instead of typing.

The rest of the facility log family

The related life-safety records are the extinguisher, emergency lighting, fire door and generator logs. The compliance calendar puts each of them on dates with the code behind it.