Skilled Nursing Facility Preventive Maintenance Checklist
A ready-to-use preventive maintenance checklist for a skilled nursing facility — measurable, code-referenced tasks grouped by frequency. Read the full checklist below, or build a version tailored to your building in under a minute.
What type of facility?
Pick the closest match — it decides which equipment the checklist starts with.
What a skilled nursing facility needs to cover
Emergency power, fire and call systems, patient lifts, and medication refrigeration are life-critical and are exactly what surveyors document.
Compliance: CMS / Life Safety Code (NFPA 101) survey documentation and NFPA 110 generator testing. 24/7 occupancy means maintenance without evacuation or service interruption.
The skilled nursing facility checklist
A typical starting checklist for a skilled nursing facility, grouped by how often each task runs. Every task has a pass/fail criterion and, where it applies, the governing standard.
Daily
- Medication refrigerationCritical — Log refrigerator temperature (36–46°F / 2–8°C); verify the out-of-range alarm is armed. Pass = temp in range, alarm active.
Weekly
- Standby generatorCritical — Visual check: no leaks, block heater on, battery charger showing green, coolant/oil normal, no active alarms.
Monthly
- Boiler(s)Critical — Verify operating pressure within manufacturer range (typ. 12–30 PSI, low-pressure hot water); check for leaks; test low-water cutoff.
- Chiller(s)Critical — Log refrigerant pressures and approach temperatures; inspect for oil or refrigerant leaks. Pass = readings within manufacturer envelope, no leaks.
- Water heater(s) / domestic hot waterCritical — Verify hot-water delivery temperature at fixtures (typ. 120°F; anti-scald limits where required). Pass = within target range.
- Emergency & egress lightingCriticalNFPA 101 — 30-second function test of every emergency light and illuminated exit sign. Pass = all illuminate on test.
- Nurse call / emergency call systemCritical — Test call stations in a rotating sample of rooms and bathrooms; verify audible and visual annunciation at the staff station. Pass = every tested station registers.
- Elevator(s)CriticalASME A17.1 — Test the emergency phone/communication and door-reversal safety; verify cab lighting and floor leveling. Pass = two-way comms works, doors reverse, cab level.
- Standby generatorCriticalNFPA 110 — 30-minute operational test under load; log run time and verify fuel level at or above the required minimum (typ. ~75%).
- Patient / ceiling lifts (Hoyer)Critical — Inspect slings, straps, and hooks for wear; test emergency lowering; verify the load-rating label is legible. Follow the manufacturer PM schedule — and in assisted living, inspect before each use. Pass = no fraying, e-lower works, rating legible.
- Air filters — Replace or clean filters; verify correct MERV rating and no air bypass around the frame. Pass = clean filter seated, airflow unobstructed.
- Grease traps / interceptors — Clean or pump per schedule; verify no blockage and lid seal intact. Log the service.
- Fire extinguishersNFPA 10 — Verify each extinguisher is present, gauge in the green, seal/pin intact, and access is clear. Pass = charged and unobstructed.
- Egress doors & exit pathsNFPA 101 — Verify exits are unobstructed, doors self-close and latch, panic hardware is operable, and paths are illuminated. Pass = free, latching egress on every path.
- Automatic transfer switch(es)NFPA 110 — Exercise the ATS through transfer and re-transfer; verify time delays and no alarms. Pass = clean transfer both directions.
- Oxygen concentrators — Verify O2 concentration and flow output, clean the intake filter, and confirm alarms function per the manufacturer PM. Pass = output and alarms within spec.
- Exterior / parking lighting — Walk the site after dark; replace failed lamps and verify photocell/timer operation. Pass = no dark zones at entries or walkways.
Quarterly
- Fire alarm systemCriticalNFPA 72 — Test a rotating sample of initiating and notification devices; verify the monitoring signal reaches the central station. Pass = signal confirmed, devices annunciate.
- Sprinkler systemCriticalNFPA 25 — Inspect gauges (system pressure normal), control valves (locked/supervised open), and alarm devices.
- Air handlers / rooftop unitsASHRAE 180 — Inspect belts, bearings, and dampers; verify supply-air temperature within ±3°F of setpoint. Pass = no glazing/cracking on belts, setpoint held.
- Air handlers / rooftop units — Clean condensate pan and drain line; confirm no standing water or overflow.
- Sump / ejector pumps — Test by filling the pit until the float trips; confirm the pump cycles, discharges, and shuts off. Pass = full cycle observed.
- Kitchen hood suppressionNFPA 96 — Inspect nozzles and blow-off caps; verify the manual pull station is accessible and unobstructed.
- Roof — Inspect membrane/flashing and clear roof drains and scuppers; document condition after major storms. Pass = drains clear, no ponding or open seams.
- Walkways & parking surfaces — Inspect for trip hazards, potholes, and heaving; verify ADA ramp condition, striping, and signage. Pass = no trip hazards on accessible routes.
- Site drainage / storm — Clear catch basins and swales; inspect after heavy rain for ponding near the building. Pass = water sheds away from structure.
- Commercial kitchen equipment — Inspect ranges, ovens, and gas connections; verify walk-ins hold temperature (cooler 35–40°F, freezer ≤0°F). Pass = temps held, no gas odor.
- Thermostats / controls — Verify calibration within ±2°F; confirm occupancy schedules and setbacks are active.
- Exhaust & ventilation fans — Confirm rotation and airflow, no excessive vibration or noise; clean grilles and screens.
- Domestic water pressure / PRV — Verify static pressure of 40–80 PSI; inspect the pressure-reducing valve for creep or leaks.
- Restroom / unit fixtures — Check for leaks, drips, and running toilets; verify shutoff valves are operable.
- GFCI / AFCI devices — Press the test button on GFCIs in wet locations; confirm trip and reset. Pass = each device trips and resets.
- Gutters & downspouts — Clear debris and verify drainage carries water away from the foundation.
- Irrigation system — Test each zone; check for leaks and broken heads and adjust the seasonal schedule. Pass = all zones fire, no visible leaks.
- Fences, gates & access control — Inspect gates, latches, and access control; verify cameras and call boxes are operable.
- Common area deep clean & inspection — Deep clean lobbies, corridors, and amenity rooms; inspect furnishings, flooring, and handrails for damage.
Annual
- Boiler(s)Critical — Combustion analysis, safety/relief valve test, and cleaning by a licensed technician.
- Water heater(s) / domestic hot waterCritical — Flush tank/sediment, test the T&P relief valve, and inspect the anode rod.
- Emergency & egress lightingCriticalNFPA 101 — 90-minute battery duration test; record any unit that fails to hold.
- Fire alarm systemCriticalNFPA 72 — Full inspection and test of all devices by a licensed fire-alarm contractor; file the report.
- Sprinkler systemCriticalNFPA 25 — Main drain test, water-flow alarm test, and full inspection by a licensed contractor.
- Smoke & CO detectorsCritical — Test each alarm; verify it is within its 10-year service life and replace batteries. Pass = audible on test, not expired.
- Elevator(s)CriticalASME A17.1 — Full inspection and load test by a licensed elevator contractor; confirm the certificate is current and posted.
- Standby generatorCriticalNFPA 110 — Where the monthly test has not loaded the set enough (NFPA 110 uses 30% of nameplate), a load-bank test at rated capacity; plus the fuel-quality test. Your AHJ or your service contract may require the load bank annually regardless.
- Condenser & evaporator coilsASHRAE 180 — Clean coils; verify temperature split of 16–22°F across the evaporator. Pass = split within range, fins clean.
- Backflow preventers — Test by a certified backflow tester; verify no back-siphonage and file the test report with the water authority.
- Electrical panels / distribution — Inspect (or thermal-scan) for hot spots, corrosion, and loose lugs; verify breakers are labeled and the directory is current. Pass = no discoloration, all circuits identified.
- Fire extinguishersNFPA 10 — Certified annual maintenance and tag by a licensed servicer.
- Kitchen hood suppressionNFPA 96 — Certified hood-suppression system inspection.
- Roof — Professional roof inspection and preventive repair.
- Dryer exhaust vents — Clean lint from dryer ducts through to the exterior termination (fire prevention). Pass = free airflow, no lint blockage.
- Exterior sealant / caulking — Inspect and reseal window and door perimeters and control joints; note any failed sealant.
- Masonry / façade — Inspect for cracks, spalling, and efflorescence; check lintels and expansion joints.
- Signage & wayfinding — Verify lit signage works, the address is visible from the street, and ADA/accessible signage is present.
Other facility types: Apartment Building · Assisted Living Facility · Independent Living Community · Behavioral Health Facility · All types
Email me when there is a new free tool Your document is ready above — print it or save it as a PDF. This is just the occasional note about new tools, and one click unsubscribes.
Last reviewed July 2026. This checklist and the free generator are informational and not legal, code, or compliance advice. Lines tagged with a standard are traceable to that published document; lines tagged Recommended are ordinary good practice with no standard cited. A consensus standard binds you only where your jurisdiction or CMS has adopted it, which we have not checked for your building. Intervals and thresholds are starting points — verify the current requirements for your facility, occupancy, and jurisdiction.
Questions people ask
- What should be on a skilled nursing facility preventive maintenance checklist?
- A skilled nursing facility PM checklist covers HVAC, plumbing, electrical, life safety, and building systems with measurable pass/fail tasks grouped by frequency. Emergency power, fire and call systems, patient lifts, and medication refrigeration are life-critical and are exactly what surveyors document. CMS / Life Safety Code (NFPA 101) survey documentation and NFPA 110 generator testing. 24/7 occupancy means maintenance without evacuation or service interruption.
- Is the checklist free?
- Yes — free, no signup, no watermark. The generator builds a checklist on your device that prints to a clean PDF.
- How often should preventive maintenance tasks be done?
- Tasks are grouped by frequency — daily, weekly, monthly, quarterly, and annual. Flag any asset that passes 110% of its scheduled interval as overdue.