Behavioral Health Facility Preventive Maintenance Checklist

A ready-to-use preventive maintenance checklist for a behavioral health facility — measurable, code-referenced tasks grouped by frequency. Read the full checklist below, or build a version tailored to your building in under a minute.

Step 1 of 50% complete

What type of facility?

Pick the closest match — it decides which equipment the checklist starts with.

What a behavioral health facility needs to cover

Anti-ligature fixture and hardware inspections, secured windows and doors, safety glazing, nurse call, and emergency power.

Compliance: Joint Commission environment-of-care and triennial emergency-power review; anti-ligature standards for patient areas.

What a behavioral health facility has that most buildings don’t

  • Anti-ligature fixtures & hardwareCritical
  • Door alarms & secured egress hardwareCritical

Everything else on the list — 35 of the 37 assets here — is the maintenance any building of this size carries, which is why a generic checklist gets you most of the way and then misses the 2 things that actually distinguish the building.

The behavioral health facility checklist

A typical starting checklist for a behavioral health facility, grouped by how often each task runs. Every task has a pass/fail criterion and, where it applies, the governing standard.

Daily

  • Medication refrigerationCriticalLog refrigerator temperature (36–46°F / 2–8°C); verify the out-of-range alarm is armed. Pass = temp in range, alarm active.

Weekly

  • Standby generatorCriticalVisual check: no leaks, block heater on, battery charger showing green, coolant/oil normal, no active alarms.

Monthly

  • Boiler(s)CriticalVerify operating pressure within manufacturer range (typ. 12–30 PSI, low-pressure hot water); check for leaks; test low-water cutoff.
  • Water heater(s) / domestic hot waterCriticalVerify hot-water delivery temperature at fixtures (typ. 120°F; anti-scald limits where required). Pass = within target range.
  • Emergency & egress lightingCriticalNFPA 10130-second function test of every emergency light and illuminated exit sign. Pass = all illuminate on test.
  • Anti-ligature fixtures & hardwareCriticalInspect patient-area fixtures, door hardware, hinges, and hooks for ligature risk; confirm safety glazing and secured windows are intact. Pass = no ligature points found.
  • Door alarms & secured egress hardwareCriticalWalk every secured exit: confirm the door alarm sounds, the release works as your building is set up for it, and the door latches again afterwards. Record any door that did not.
  • Door alarms & secured egress hardwareCriticalConfirm keypads, fobs or delayed-egress hardware are working at every secured door and that staff know the release. Record anything out of service.
  • Nurse call / emergency call systemCriticalTest call stations in a rotating sample of rooms and bathrooms; verify audible and visual annunciation at the staff station. Pass = every tested station registers.
  • Elevator(s)CriticalASME A17.1Test the emergency phone/communication and door-reversal safety; verify cab lighting and floor leveling. Pass = two-way comms works, doors reverse, cab level.
  • Standby generatorCriticalNFPA 11030-minute operational test under load; log run time and verify fuel level at or above the required minimum (typ. ~75%).
  • Air filtersReplace or clean filters; verify correct MERV rating and no air bypass around the frame. Pass = clean filter seated, airflow unobstructed.
  • Fire extinguishersNFPA 10Verify each extinguisher is present, gauge in the green, seal/pin intact, and access is clear. Pass = charged and unobstructed.
  • Egress doors & exit pathsNFPA 101Verify exits are unobstructed, doors self-close and latch, panic hardware is operable, and paths are illuminated. Pass = free, latching egress on every path.
  • Automatic transfer switch(es)NFPA 110Exercise the ATS through transfer and re-transfer; verify time delays and no alarms. Pass = clean transfer both directions.
  • Exterior / parking lightingWalk the site after dark; replace failed lamps and verify photocell/timer operation. Pass = no dark zones at entries or walkways.

Quarterly

  • Fire alarm systemCriticalNFPA 72Test a rotating sample of initiating and notification devices; verify the monitoring signal reaches the central station. Pass = signal confirmed, devices annunciate.
  • Sprinkler systemCriticalNFPA 25Inspect gauges (system pressure normal), control valves (locked/supervised open), and alarm devices.
  • Air handlers / rooftop unitsASHRAE 180Inspect belts, bearings, and dampers; verify supply-air temperature within ±3°F of setpoint. Pass = no glazing/cracking on belts, setpoint held.
  • Air handlers / rooftop unitsClean condensate pan and drain line; confirm no standing water or overflow.
  • Sump / ejector pumpsTest by filling the pit until the float trips; confirm the pump cycles, discharges, and shuts off. Pass = full cycle observed.
  • RoofInspect membrane/flashing and clear roof drains and scuppers; document condition after major storms. Pass = drains clear, no ponding or open seams.
  • Walkways & parking surfacesInspect for trip hazards, potholes, and heaving; verify ADA ramp condition, striping, and signage. Pass = no trip hazards on accessible routes.
  • Site drainage / stormClear catch basins and swales; inspect after heavy rain for ponding near the building. Pass = water sheds away from structure.
  • Thermostats / controlsVerify calibration within ±2°F; confirm occupancy schedules and setbacks are active.
  • Exhaust & ventilation fansConfirm rotation and airflow, no excessive vibration or noise; clean grilles and screens.
  • Domestic water pressure / PRVVerify static pressure of 40–80 PSI; inspect the pressure-reducing valve for creep or leaks.
  • Restroom / unit fixturesCheck for leaks, drips, and running toilets; verify shutoff valves are operable.
  • GFCI / AFCI devicesPress the test button on GFCIs in wet locations; confirm trip and reset. Pass = each device trips and resets.
  • Gutters & downspoutsClear debris and verify drainage carries water away from the foundation.
  • Irrigation systemTest each zone; check for leaks and broken heads and adjust the seasonal schedule. Pass = all zones fire, no visible leaks.
  • Fences, gates & access controlInspect gates, latches, and access control; verify cameras and call boxes are operable.
  • Common area deep clean & inspectionDeep clean lobbies, corridors, and amenity rooms; inspect furnishings, flooring, and handrails for damage.

Annual

  • Boiler(s)CriticalCombustion analysis, safety/relief valve test, and cleaning by a licensed technician.
  • Water heater(s) / domestic hot waterCriticalFlush tank/sediment, test the T&P relief valve, and inspect the anode rod.
  • Emergency & egress lightingCriticalNFPA 10190-minute battery duration test; record any unit that fails to hold.
  • Fire alarm systemCriticalNFPA 72Full inspection and test of all devices by a licensed fire-alarm contractor; file the report.
  • Sprinkler systemCriticalNFPA 25Main drain test, water-flow alarm test, and full inspection by a licensed contractor.
  • Smoke & CO detectorsCriticalTest each alarm; verify it is within its 10-year service life and replace batteries. Pass = audible on test, not expired.
  • Elevator(s)CriticalASME A17.1Full inspection and load test by a licensed elevator contractor; confirm the certificate is current and posted.
  • Standby generatorCriticalNFPA 110Where the monthly test has not loaded the set enough (NFPA 110 uses 30% of nameplate), a load-bank test at rated capacity; plus the fuel-quality test. Your AHJ or your service contract may require the load bank annually regardless.
  • Condenser & evaporator coilsASHRAE 180Clean coils; verify temperature split of 16–22°F across the evaporator. Pass = split within range, fins clean.
  • Backflow preventersTest by a certified backflow tester; verify no back-siphonage and file the test report with the water authority.
  • Electrical panels / distributionInspect (or thermal-scan) for hot spots, corrosion, and loose lugs; verify breakers are labeled and the directory is current. Pass = no discoloration, all circuits identified.
  • Fire extinguishersNFPA 10Certified annual maintenance and tag by a licensed servicer.
  • RoofProfessional roof inspection and preventive repair.
  • Exterior sealant / caulkingInspect and reseal window and door perimeters and control joints; note any failed sealant.
  • Masonry / façadeInspect for cracks, spalling, and efflorescence; check lintels and expansion joints.
  • Signage & wayfindingVerify lit signage works, the address is visible from the street, and ADA/accessible signage is present.

Build this as an editable PDF →

Other facility types: Apartment Building · Skilled Nursing Facility · Assisted Living Facility · Independent Living Community · All types

Email me when there is a new free tool Your document is ready above — print it or save it as a PDF. This is just the occasional note about new tools, and one click unsubscribes.

Last reviewed July 2026. This checklist and the free generator are informational and not legal, code, or compliance advice. Lines tagged with a standard are traceable to that published document; lines tagged Recommended are ordinary good practice with no standard cited. A consensus standard binds you only where your jurisdiction or CMS has adopted it, which we have not checked for your building. Intervals and thresholds are starting points — verify the current requirements for your facility, occupancy, and jurisdiction.

Questions people ask

What should be on a behavioral health facility preventive maintenance checklist?
A behavioral health facility PM checklist covers HVAC, plumbing, electrical, life safety, and building systems with measurable pass/fail tasks grouped by frequency. Anti-ligature fixture and hardware inspections, secured windows and doors, safety glazing, nurse call, and emergency power. Joint Commission environment-of-care and triennial emergency-power review; anti-ligature standards for patient areas.
Is the checklist free?
Yes — free, no signup, no watermark. The generator builds a checklist on your device that prints to a clean PDF.
How often should preventive maintenance tasks be done?
Tasks are grouped by frequency — daily, weekly, monthly, quarterly, and annual. Flag any asset that passes 110% of its scheduled interval as overdue.