Hospital & Medical Facility Preventive Maintenance Checklist

A ready-to-use preventive maintenance checklist for a hospital & medical facility — measurable, code-referenced tasks grouped by frequency. Read the full checklist below, or build a version tailored to your building in under a minute.

Step 1 of 50% complete

What type of facility?

Pick the closest match — it decides which equipment the checklist starts with.

What a hospital & medical facility needs to cover

Level 1 generators, medical gas, negative-pressure isolation rooms, chillers, and fire systems.

Compliance: Joint Commission environment-of-care documentation, NFPA 110 Level 1 generator testing, NFPA 99 medical gas, and ASHRAE 170/180 HVAC standards.

What a hospital & medical facility has that most buildings don’t

  • Cooling tower
  • Negative-pressure / isolation roomsCritical
  • Medical gas & vacuum systemsCritical
  • UPS / battery backup systems

Everything else on the list — 41 of the 45 assets here — is the maintenance any building of this size carries, which is why a generic checklist gets you most of the way and then misses the 4 things that actually distinguish the building.

The hospital & medical facility checklist

A typical starting checklist for a hospital & medical facility, grouped by how often each task runs. Every task has a pass/fail criterion and, where it applies, the governing standard.

Daily

  • Negative-pressure / isolation roomsCriticalASHRAE 170Verify and log pressure differential (≥0.01 in. w.c. negative to corridor). Pass = negative differential confirmed on each room.
  • Medication refrigerationCriticalLog refrigerator temperature (36–46°F / 2–8°C); verify the out-of-range alarm is armed. Pass = temp in range, alarm active.

Weekly

  • Standby generatorCriticalVisual check: no leaks, block heater on, battery charger showing green, coolant/oil normal, no active alarms.

Monthly

  • Boiler(s)CriticalVerify operating pressure within manufacturer range (typ. 12–30 PSI, low-pressure hot water); check for leaks; test low-water cutoff.
  • Chiller(s)CriticalLog refrigerant pressures and approach temperatures; inspect for oil or refrigerant leaks. Pass = readings within manufacturer envelope, no leaks.
  • Water heater(s) / domestic hot waterCriticalVerify hot-water delivery temperature at fixtures (typ. 120°F; anti-scald limits where required). Pass = within target range.
  • Medical gas & vacuum systemsCriticalNFPA 99Verify area alarm panels, zone valves, and source pressures per NFPA 99; confirm no active alarms. Pass = all zones normal.
  • Emergency & egress lightingCriticalNFPA 10130-second function test of every emergency light and illuminated exit sign. Pass = all illuminate on test.
  • Nurse call / emergency call systemCriticalTest call stations in a rotating sample of rooms and bathrooms; verify audible and visual annunciation at the staff station. Pass = every tested station registers.
  • Elevator(s)CriticalASME A17.1Test the emergency phone/communication and door-reversal safety; verify cab lighting and floor leveling. Pass = two-way comms works, doors reverse, cab level.
  • Standby generatorCriticalNFPA 11030-minute operational test under load; log run time and verify fuel level at or above the required minimum (typ. ~75%).
  • Patient / ceiling lifts (Hoyer)CriticalInspect slings, straps, and hooks for wear; test emergency lowering; verify the load-rating label is legible. Follow the manufacturer PM schedule — and in assisted living, inspect before each use. Pass = no fraying, e-lower works, rating legible.
  • Air filtersReplace or clean filters; verify correct MERV rating and no air bypass around the frame. Pass = clean filter seated, airflow unobstructed.
  • Cooling towerCheck water-treatment / biocide levels and clean basin; document Legionella-control steps.
  • Grease traps / interceptorsClean or pump per schedule; verify no blockage and lid seal intact. Log the service.
  • Fire extinguishersNFPA 10Verify each extinguisher is present, gauge in the green, seal/pin intact, and access is clear. Pass = charged and unobstructed.
  • Egress doors & exit pathsNFPA 101Verify exits are unobstructed, doors self-close and latch, panic hardware is operable, and paths are illuminated. Pass = free, latching egress on every path.
  • Automatic transfer switch(es)NFPA 110Exercise the ATS through transfer and re-transfer; verify time delays and no alarms. Pass = clean transfer both directions.
  • Oxygen concentratorsVerify O2 concentration and flow output, clean the intake filter, and confirm alarms function per the manufacturer PM. Pass = output and alarms within spec.
  • Exterior / parking lightingWalk the site after dark; replace failed lamps and verify photocell/timer operation. Pass = no dark zones at entries or walkways.

Quarterly

  • Fire alarm systemCriticalNFPA 72Test a rotating sample of initiating and notification devices; verify the monitoring signal reaches the central station. Pass = signal confirmed, devices annunciate.
  • Sprinkler systemCriticalNFPA 25Inspect gauges (system pressure normal), control valves (locked/supervised open), and alarm devices.
  • Air handlers / rooftop unitsASHRAE 180Inspect belts, bearings, and dampers; verify supply-air temperature within ±3°F of setpoint. Pass = no glazing/cracking on belts, setpoint held.
  • Air handlers / rooftop unitsClean condensate pan and drain line; confirm no standing water or overflow.
  • Sump / ejector pumpsTest by filling the pit until the float trips; confirm the pump cycles, discharges, and shuts off. Pass = full cycle observed.
  • Kitchen hood suppressionNFPA 96Inspect nozzles and blow-off caps; verify the manual pull station is accessible and unobstructed.
  • UPS / battery backup systemsVerify battery health (no swelling or corrosion) and confirm expected runtime on self-test. Pass = self-test passes, batteries within service life.
  • RoofInspect membrane/flashing and clear roof drains and scuppers; document condition after major storms. Pass = drains clear, no ponding or open seams.
  • Walkways & parking surfacesInspect for trip hazards, potholes, and heaving; verify ADA ramp condition, striping, and signage. Pass = no trip hazards on accessible routes.
  • Site drainage / stormClear catch basins and swales; inspect after heavy rain for ponding near the building. Pass = water sheds away from structure.
  • Commercial kitchen equipmentInspect ranges, ovens, and gas connections; verify walk-ins hold temperature (cooler 35–40°F, freezer ≤0°F). Pass = temps held, no gas odor.
  • Thermostats / controlsVerify calibration within ±2°F; confirm occupancy schedules and setbacks are active.
  • Exhaust & ventilation fansConfirm rotation and airflow, no excessive vibration or noise; clean grilles and screens.
  • Domestic water pressure / PRVVerify static pressure of 40–80 PSI; inspect the pressure-reducing valve for creep or leaks.
  • Restroom / unit fixturesCheck for leaks, drips, and running toilets; verify shutoff valves are operable.
  • GFCI / AFCI devicesPress the test button on GFCIs in wet locations; confirm trip and reset. Pass = each device trips and resets.
  • Gutters & downspoutsClear debris and verify drainage carries water away from the foundation.
  • Irrigation systemTest each zone; check for leaks and broken heads and adjust the seasonal schedule. Pass = all zones fire, no visible leaks.
  • Fences, gates & access controlInspect gates, latches, and access control; verify cameras and call boxes are operable.
  • Common area deep clean & inspectionDeep clean lobbies, corridors, and amenity rooms; inspect furnishings, flooring, and handrails for damage.

Annual

  • Boiler(s)CriticalCombustion analysis, safety/relief valve test, and cleaning by a licensed technician.
  • Water heater(s) / domestic hot waterCriticalFlush tank/sediment, test the T&P relief valve, and inspect the anode rod.
  • Emergency & egress lightingCriticalNFPA 10190-minute battery duration test; record any unit that fails to hold.
  • Fire alarm systemCriticalNFPA 72Full inspection and test of all devices by a licensed fire-alarm contractor; file the report.
  • Sprinkler systemCriticalNFPA 25Main drain test, water-flow alarm test, and full inspection by a licensed contractor.
  • Smoke & CO detectorsCriticalTest each alarm; verify it is within its 10-year service life and replace batteries. Pass = audible on test, not expired.
  • Elevator(s)CriticalASME A17.1Full inspection and load test by a licensed elevator contractor; confirm the certificate is current and posted.
  • Standby generatorCriticalNFPA 110Where the monthly test has not loaded the set enough (NFPA 110 uses 30% of nameplate), a load-bank test at rated capacity; plus the fuel-quality test. Your AHJ or your service contract may require the load bank annually regardless.
  • Condenser & evaporator coilsASHRAE 180Clean coils; verify temperature split of 16–22°F across the evaporator. Pass = split within range, fins clean.
  • Backflow preventersTest by a certified backflow tester; verify no back-siphonage and file the test report with the water authority.
  • Electrical panels / distributionInspect (or thermal-scan) for hot spots, corrosion, and loose lugs; verify breakers are labeled and the directory is current. Pass = no discoloration, all circuits identified.
  • Fire extinguishersNFPA 10Certified annual maintenance and tag by a licensed servicer.
  • Kitchen hood suppressionNFPA 96Certified hood-suppression system inspection.
  • RoofProfessional roof inspection and preventive repair.
  • Exterior sealant / caulkingInspect and reseal window and door perimeters and control joints; note any failed sealant.
  • Masonry / façadeInspect for cracks, spalling, and efflorescence; check lintels and expansion joints.
  • Signage & wayfindingVerify lit signage works, the address is visible from the street, and ADA/accessible signage is present.

Build this as an editable PDF →

Other facility types: Apartment Building · Skilled Nursing Facility · Assisted Living Facility · Independent Living Community · All types

Email me when there is a new free tool Your document is ready above — print it or save it as a PDF. This is just the occasional note about new tools, and one click unsubscribes.

Last reviewed July 2026. This checklist and the free generator are informational and not legal, code, or compliance advice. Lines tagged with a standard are traceable to that published document; lines tagged Recommended are ordinary good practice with no standard cited. A consensus standard binds you only where your jurisdiction or CMS has adopted it, which we have not checked for your building. Intervals and thresholds are starting points — verify the current requirements for your facility, occupancy, and jurisdiction.

Questions people ask

What should be on a hospital & medical facility preventive maintenance checklist?
A hospital & medical facility PM checklist covers HVAC, plumbing, electrical, life safety, and building systems with measurable pass/fail tasks grouped by frequency. Level 1 generators, medical gas, negative-pressure isolation rooms, chillers, and fire systems. Joint Commission environment-of-care documentation, NFPA 110 Level 1 generator testing, NFPA 99 medical gas, and ASHRAE 170/180 HVAC standards.
Is the checklist free?
Yes — free, no signup, no watermark. The generator builds a checklist on your device that prints to a clean PDF.
How often should preventive maintenance tasks be done?
Tasks are grouped by frequency — daily, weekly, monthly, quarterly, and annual. Flag any asset that passes 110% of its scheduled interval as overdue.