Hospital & Medical Facility Preventive Maintenance Checklist

A ready-to-use preventive maintenance checklist for a hospital & medical facility — measurable, code-referenced tasks grouped by frequency. Read the full checklist below, or build a version tailored to your building in under a minute.

Step 1 of 50% complete

What type of facility?

Pick the closest match — it decides which equipment the checklist starts with.

What a hospital & medical facility needs to cover

Level 1 generators, medical gas, negative-pressure isolation rooms, chillers, and fire systems.

Compliance: Joint Commission environment-of-care documentation, NFPA 110 Level 1 generator testing, NFPA 99 medical gas, and ASHRAE 170/180 HVAC standards.

The hospital & medical facility checklist

A typical starting checklist for a hospital & medical facility, grouped by how often each task runs. Every task has a pass/fail criterion and, where it applies, the governing standard.

Daily

  • Negative-pressure / isolation roomsCriticalASHRAE 170Verify and log pressure differential (≥0.01 in. w.c. negative to corridor). Pass = negative differential confirmed on each room.
  • Medication refrigerationCriticalLog refrigerator temperature (36–46°F / 2–8°C); verify the out-of-range alarm is armed. Pass = temp in range, alarm active.

Weekly

  • Standby generatorCriticalVisual check: no leaks, block heater on, battery charger showing green, coolant/oil normal, no active alarms.

Monthly

  • Boiler(s)CriticalVerify operating pressure within manufacturer range (typ. 12–30 PSI, low-pressure hot water); check for leaks; test low-water cutoff.
  • Chiller(s)CriticalLog refrigerant pressures and approach temperatures; inspect for oil or refrigerant leaks. Pass = readings within manufacturer envelope, no leaks.
  • Water heater(s) / domestic hot waterCriticalVerify hot-water delivery temperature at fixtures (typ. 120°F; anti-scald limits where required). Pass = within target range.
  • Medical gas & vacuum systemsCriticalNFPA 99Verify area alarm panels, zone valves, and source pressures per NFPA 99; confirm no active alarms. Pass = all zones normal.
  • Emergency & egress lightingCriticalNFPA 10130-second function test of every emergency light and illuminated exit sign. Pass = all illuminate on test.
  • Nurse call / emergency call systemCriticalTest call stations in a rotating sample of rooms and bathrooms; verify audible and visual annunciation at the staff station. Pass = every tested station registers.
  • Elevator(s)CriticalASME A17.1Test the emergency phone/communication and door-reversal safety; verify cab lighting and floor leveling. Pass = two-way comms works, doors reverse, cab level.
  • Standby generatorCriticalNFPA 11030-minute operational test under load; log run time and verify fuel level at or above the required minimum (typ. ~75%).
  • Patient / ceiling lifts (Hoyer)CriticalInspect slings, straps, and hooks for wear; test emergency lowering; verify the load-rating label is legible. Follow the manufacturer PM schedule — and in assisted living, inspect before each use. Pass = no fraying, e-lower works, rating legible.
  • Air filtersReplace or clean filters; verify correct MERV rating and no air bypass around the frame. Pass = clean filter seated, airflow unobstructed.
  • Cooling towerCheck water-treatment / biocide levels and clean basin; document Legionella-control steps.
  • Grease traps / interceptorsClean or pump per schedule; verify no blockage and lid seal intact. Log the service.
  • Fire extinguishersNFPA 10Verify each extinguisher is present, gauge in the green, seal/pin intact, and access is clear. Pass = charged and unobstructed.
  • Egress doors & exit pathsNFPA 101Verify exits are unobstructed, doors self-close and latch, panic hardware is operable, and paths are illuminated. Pass = free, latching egress on every path.
  • Automatic transfer switch(es)NFPA 110Exercise the ATS through transfer and re-transfer; verify time delays and no alarms. Pass = clean transfer both directions.
  • Oxygen concentratorsVerify O2 concentration and flow output, clean the intake filter, and confirm alarms function per the manufacturer PM. Pass = output and alarms within spec.
  • Exterior / parking lightingWalk the site after dark; replace failed lamps and verify photocell/timer operation. Pass = no dark zones at entries or walkways.

Quarterly

  • Fire alarm systemCriticalNFPA 72Test a rotating sample of initiating and notification devices; verify the monitoring signal reaches the central station. Pass = signal confirmed, devices annunciate.
  • Sprinkler systemCriticalNFPA 25Inspect gauges (system pressure normal), control valves (locked/supervised open), and alarm devices.
  • Air handlers / rooftop unitsASHRAE 180Inspect belts, bearings, and dampers; verify supply-air temperature within ±3°F of setpoint. Pass = no glazing/cracking on belts, setpoint held.
  • Air handlers / rooftop unitsClean condensate pan and drain line; confirm no standing water or overflow.
  • Sump / ejector pumpsTest by filling the pit until the float trips; confirm the pump cycles, discharges, and shuts off. Pass = full cycle observed.
  • Kitchen hood suppressionNFPA 96Inspect nozzles and blow-off caps; verify the manual pull station is accessible and unobstructed.
  • UPS / battery backup systemsVerify battery health (no swelling or corrosion) and confirm expected runtime on self-test. Pass = self-test passes, batteries within service life.
  • RoofInspect membrane/flashing and clear roof drains and scuppers; document condition after major storms. Pass = drains clear, no ponding or open seams.
  • Walkways & parking surfacesInspect for trip hazards, potholes, and heaving; verify ADA ramp condition, striping, and signage. Pass = no trip hazards on accessible routes.
  • Site drainage / stormClear catch basins and swales; inspect after heavy rain for ponding near the building. Pass = water sheds away from structure.
  • Commercial kitchen equipmentInspect ranges, ovens, and gas connections; verify walk-ins hold temperature (cooler 35–40°F, freezer ≤0°F). Pass = temps held, no gas odor.
  • Thermostats / controlsVerify calibration within ±2°F; confirm occupancy schedules and setbacks are active.
  • Exhaust & ventilation fansConfirm rotation and airflow, no excessive vibration or noise; clean grilles and screens.
  • Domestic water pressure / PRVVerify static pressure of 40–80 PSI; inspect the pressure-reducing valve for creep or leaks.
  • Restroom / unit fixturesCheck for leaks, drips, and running toilets; verify shutoff valves are operable.
  • GFCI / AFCI devicesPress the test button on GFCIs in wet locations; confirm trip and reset. Pass = each device trips and resets.
  • Gutters & downspoutsClear debris and verify drainage carries water away from the foundation.
  • Irrigation systemTest each zone; check for leaks and broken heads and adjust the seasonal schedule. Pass = all zones fire, no visible leaks.
  • Fences, gates & access controlInspect gates, latches, and access control; verify cameras and call boxes are operable.
  • Common area deep clean & inspectionDeep clean lobbies, corridors, and amenity rooms; inspect furnishings, flooring, and handrails for damage.

Annual

  • Boiler(s)CriticalCombustion analysis, safety/relief valve test, and cleaning by a licensed technician.
  • Water heater(s) / domestic hot waterCriticalFlush tank/sediment, test the T&P relief valve, and inspect the anode rod.
  • Emergency & egress lightingCriticalNFPA 10190-minute battery duration test; record any unit that fails to hold.
  • Fire alarm systemCriticalNFPA 72Full inspection and test of all devices by a licensed fire-alarm contractor; file the report.
  • Sprinkler systemCriticalNFPA 25Main drain test, water-flow alarm test, and full inspection by a licensed contractor.
  • Smoke & CO detectorsCriticalTest each alarm; verify it is within its 10-year service life and replace batteries. Pass = audible on test, not expired.
  • Elevator(s)CriticalASME A17.1Full inspection and load test by a licensed elevator contractor; confirm the certificate is current and posted.
  • Standby generatorCriticalNFPA 110Annual load-bank test (3-hour, Level 1 where required) and fuel-quality test.
  • Condenser & evaporator coilsASHRAE 180Clean coils; verify temperature split of 16–22°F across the evaporator. Pass = split within range, fins clean.
  • Backflow preventersTest by a certified backflow tester; verify no back-siphonage and file the test report with the water authority.
  • Electrical panels / distributionInspect (or thermal-scan) for hot spots, corrosion, and loose lugs; verify breakers are labeled and the directory is current. Pass = no discoloration, all circuits identified.
  • Fire extinguishersNFPA 10Certified annual maintenance and tag by a licensed servicer.
  • Kitchen hood suppressionNFPA 96Certified hood-suppression system inspection.
  • RoofProfessional roof inspection and preventive repair.
  • Exterior sealant / caulkingInspect and reseal window and door perimeters and control joints; note any failed sealant.
  • Masonry / façadeInspect for cracks, spalling, and efflorescence; check lintels and expansion joints.
  • Signage & wayfindingVerify lit signage works, the address is visible from the street, and ADA/accessible signage is present.

Build this as an editable PDF →

Questions

What should be on a hospital & medical facility PM checklist?

Level 1 generators, medical gas, negative-pressure isolation rooms, chillers, and fire systems. Joint Commission environment-of-care documentation, NFPA 110 Level 1 generator testing, NFPA 99 medical gas, and ASHRAE 170/180 HVAC standards.

How often should these tasks be done?

Tasks are grouped by frequency — daily, weekly, monthly, quarterly, and annual. Flag any asset that passes 110% of its scheduled interval as overdue; silent drift is the top cause of missed PM.

Is it really free?

Yes — free, no signup, no watermark. The generator builds a checklist on your device that prints to a clean PDF.

Other facility types: Apartment Building · Skilled Nursing Facility · Assisted Living Facility · Independent Living Community · All types

Want to hear when we launch a new free tool? No spam — a few emails a year, unsubscribe anytime.

Last reviewed July 2026. This checklist and the free generator are informational and not legal, code, or compliance advice. Intervals and thresholds are typical starting points — verify the current requirements for your facility, occupancy, and jurisdiction.